Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL

Pagina creata da Roberta Pastore
 
CONTINUA A LEGGERE
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
CO2
High efficiency condensing unit

     Manuale d’uso OEM

                                                                  NO POWER
                                                                   & SIGNAL
                                                                    CABLES
                                                                  TOGETHER
                                               READ CAREFULLY IN THE TEXT!

        Integrated Control Solutions & Energy Savings
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
ITA
                               AVVERTENZE                                                                                 ATTENZIONE
                                                                                                                                           NO POWER
                                                                                                                                            & SIGNAL
                                                                                                                                             CABLES
                                                                                                                                           TOGETHER
                                                                                                                       READ CAREFULLY IN THE TEXT!
CAREL basa lo sviluppo dei suoi prodotti su una esperienza pluridecennale nel
campo HVAC, sull’investimento continuo in innovazione tecnologica di prodotto,              Separare quanto più possibile i cavi delle sonde e degli ingressi digitali dai cavi
su procedure e processi di qualità rigorosi con test in-circuit e funzionali sul 100%       dei carichi induttivi e di potenza per evitare possibili disturbi elettromagnetici.
della sua produzione, sulle più innovative tecnologie di produzione disponibili             Non inserire mai nelle stesse canaline (comprese quelle dei quadri elettrici)
nel mercato. CAREL e le sue filiali/affiliate non garantiscono tuttavia che tutti              cavi di potenza e cavi di segnale.
gli aspetti del prodotto e del software incluso nel prodotto risponderanno alle
esigenze dell’applicazione finale, pur essendo il prodotto costruito secondo le
tecniche dello stato dell’arte. Il cliente (costruttore, progettista o installatore
dell’equipaggiamento finale) si assume ogni responsabilità e rischio in relazione                                         SMALTIMENTO
alla configurazione del prodotto per il raggiungimento dei risultati previsti in
relazione all’installazione e/o equipaggiamento finale specifico. CAREL in questo
caso, previ accordi specifici, può intervenire come consulente per la buona
riuscita dello start-up macchina finale/applicazione, ma in nessun caso può
essere ritenuta responsabile per il buon funzionamento dell’ equipaggiamento/
impianto finale.                                                                             INFORMAZIONE AGLI UTENTI PER IL CORRETTO TRATTAMENTO DEI RIFIUTI DI
                                                                                            APPARECCHIATURE ELETTRICHE ED ELETTRONICHE (RAEE)
Il prodotto CAREL è un prodotto avanzato, il cui funzionamento è specificato
nella documentazione tecnica fornita col prodotto o scaricabile, anche                      In riferimento alla Direttiva 2002/96/CE del Parlamento Europeo e del
anteriormente all’acquisto, dal sito internet www.carel.com.                                Consiglio del 27 gennaio 2003 e alle relative normative nazionali di attuazione,
Ogni prodotto CAREL, in relazione al suo avanzato livello tecnologico, necessita            Vi informiamo che:
di una fase di qualifica / configurazione / programmazione / commissioning                    • sussiste l’obbligo di non smaltire i RAEE come rifiuti urbani e di effettuare,
affinché possa funzionare al meglio per l’applicazione specifica. La mancanza di                   per detti rifiuti, una raccolta separata;
tale fase di studio, come indicata nel manuale, può generare malfunzionamenti               • per lo smaltimento vanno utilizzati i sistemi di raccolta pubblici o privati
nei prodotti finali di cui CAREL non potrà essere ritenuta responsabile. Soltanto                previsti dalla leggi locali. È inoltre possibile riconsegnare al distributore
personale qualificato può installare o eseguire interventi di assistenza tecnica                 l’apparecchiatura a fine vita in caso di acquisto di una nuova;
sul prodotto. Il cliente finale deve usare il prodotto solo nelle modalità descritte         • questa apparecchiatura può contenere sostanze pericolose: un uso
nella documentazione relativa al prodotto stesso.                                               improprio o uno smaltimento non corretto potrebbe avere effetti negativi
                                                                                                sulla salute umana e sull’ambiente;
Senza che ciò escluda la doverosa osservanza di ulteriori avvertenze presenti               • il simbolo (contenitore di spazzatura su ruote barrato) riportato sul prodotto
nel manuale, si evidenza che è in ogni caso necessario, per ciascun Prodotto                    o sulla confezione e sul foglio istruzioni indica che l’apparecchiatura è stata
di CAREL:                                                                                       immessa sul mercato dopo il 13 agosto 2005 e che deve essere oggetto di
• evitare che i circuiti elettronici si bagnino. La pioggia, l’umidità e tutti i                raccolta separata;
   tipi di liquidi o la condensa contengono sostanze minerali corrosive che                 • in caso di smaltimento abusivo dei rifiuti elettrici ed elettronici sono previste
   possono danneggiare i circuiti elettronici. In ogni caso il prodotto va usato                sanzioni stabilite dalle vigenti normative locali in materia di smaltimento.
   o stoccato in ambienti che rispettano i limiti di temperatura ed umidità
   specificati nel manuale;                                                                  Garanzia sui materiali: 2 anni (dalla data di produzione, escluse le parti di
• non installare il dispositivo in ambienti particolarmente caldi. Temperature              consumo).
   troppo elevate possono ridurre la durata dei dispositivi elettronici,
   danneggiarli e deformare o fondere le parti in plastica. In ogni caso                    Omologazioni: la qualità e la sicurezza dei prodotti CAREL S.P.A. sono garantite
   il prodotto va usato o stoccato in ambienti che rispettano i limiti di                   dal sistema di progettazione e produzione certificato ISO 9001.
   temperatura ed umidità specificati nel manuale;
• non tentare di aprire il dispositivo in modi diversi da quelli indicati nel
   manuale;
• non fare cadere, battere o scuotere il dispositivo, poiché i circuiti interni e i
   meccanismi potrebbero subire danni irreparabili;
• non usare prodotti chimici corrosivi, solventi o detergenti aggressivi per
   pulire il dispositivo;
• non utilizzare il prodotto in ambiti applicativi diversi da quanto specificato
   nel manuale tecnico.
Tutti i suggerimenti sopra riportati sono validi altresì per il controllo, schede
seriali, chiavi di programmazione o comunque per qualunque altro accessorio
del portfolio prodotti CAREL. CAREL adotta una politica di continuo sviluppo.
Pertanto CAREL si riserva il diritto di effettuare modifiche e miglioramenti a
qualsiasi prodotto descritto nel presente documento senza previo preavviso.
I dati tecnici presenti nel manuale possono subire modifiche senza obbligo
di preavviso.
La responsabilità di CAREL in relazione al proprio prodotto è regolata dalle
condizioni generali di contratto CAREL editate nel sito www.carel.com e/o
da specifici accordi con i clienti; in particolare, nella misura consentita dalla
normativa applicabile, in nessun caso CAREL, i suoi dipendenti o le sue filiali/
affiliate saranno responsabili di eventuali mancati guadagni o vendite, perdite
di dati e di informazioni, costi di merci o servizi sostitutivi, danni a cose o
persone, interruzioni di attività, o eventuali danni diretti, indiretti, incidentali,
patrimoniali, di copertura, punitivi, speciali o consequenziali in qualunque
modo causati, siano essi contrattuali, extra contrattuali o dovuti a negligenza
o altra responsabilità derivanti dall’installazione, utilizzo o impossibilità di
utilizzo del prodotto, anche se CAREL o le sue filiali/affiliate siano state avvisate
della possibilità di danni.

                                                                                        3                                         Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
ITA

Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019   4
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
ITA
Indice

1. INTRODUZIONE                                                                                                             7
 1.1 Caratteristiche generali .................................................................................. 7
 1.2 Componenti e accessori ................................................................................ 7

2. INSTALLAZIONE                                                                                                            8
 2.1     Scheda base: descrizione dei morsetti ....................................................... 8
 2.2     Inverter monofase 10A .................................................................................. 9
 2.3     Inverter monofase 12-16 A, trifase 18-24 A ............................................. 10
 2.4     Inverter monofase 12A PSD2 ..................................................................... 11
 2.5     Inverter 15 A 1PH e 18 A 3PH PSD2......................................................... 12
 2.6     Sonde di pressione (SPKT00**8C0) ........................................................ 14
 2.7     Sonde di temperatura .................................................................................. 14
 2.8     Schema generale di collegamento............................................................ 15
 2.9     Schemi funzionali.......................................................................................... 16
 2.10    Installazione.................................................................................................... 18

3. INTERFACCIA UTENTE                                                                                                    19
 3.1 Terminale grafico........................................................................................... 19
 3.2 Descrizione display ....................................................................................... 19

4. DESCRIZIONE MENU                                                                                                      20
 4.1 Menu principale ............................................................................................20

5. MESSA IN SERVIZIO                                                                                                     21
 5.1 Procedura guidata di messa in servizio ................................................... 21

6. FUNZIONI                                                                                                              22
 6.1     ON/OFF dell’unità ........................................................................................22
 6.2     Compressore BLDC ......................................................................................22
 6.3     Regolazione compressore ...........................................................................25
 6.4     Gestione compressori nelle unità BT/LT (DSS e Indipendente) ........27
 6.5     Ventilatori ........................................................................................................28
 6.6     Gestione dell’olio ..........................................................................................29
 6.7     Gestione valvola HPV .................................................................................32
 6.8     Gestione valvola RPRV .................................................................................33
 6.9     Funzioni generiche .......................................................................................34
 6.10    Gestione dei valori di default .....................................................................35

7. FAST COMMISSIONING                                                                                                    36
 7.1     Configurazione degli MPXPRO (versione SW t 4.0) .........................36
 7.2     Configurazione degli Ultracella (versione SW t 2.0) .........................38
 7.3     Avviamento modulo Ultra EVD EVO ........................................................43
 7.4     Connessione degli MPXPRO/Ultracella a Hecu......................................44

8. SEGNALAZIONI E ALLARMI                                                                                                47
 8.1     Gestione degli allarmi .................................................................................. 47
 8.2     Allarmi dei compressori............................................................................... 47
 8.3     Allarmi di pressione ......................................................................................48
 8.4      Allarme anti liquid return MPX valve .......................................................49
 8.5     Prevent di alta pressione .............................................................................49
 8.6     Allarmi degli MPXPRO/Ultracella ...............................................................49
 8.7     Tabella allarmi ................................................................................................50

9. AGGIORNAMENTO DEL SOFTWARE                                                                                            58
 9.1 Aggiornamento del software (Upload) ....................................................58
 9.2 Cronologia delle revisioni software........................................................... 61

                                                                                                                                  5   Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
ITA

                                                           1. INTRODUZIONE
1.1 Caratteristiche generali                                                                1.2 Componenti e accessori
Hecu CO2 è un sistema di regolazione per la gestione completa di una                          Codice              Descrizione
Condensing Unit a R744 dotata di compressore BLDC. La connessione                           A ECU70TS0C0          Hecu CO2 controller, 230Vac, RTC, 2 unipolar EEV,
seriale tra Condensing Unit ed evaporatori dotati di MPX PRO/Ultracella e                                         connector kit, no BMS, FLSMTDMCUTU
valvole di espansione CAREL EEV costituisce uno degli elementi principali                   A ECU70TS0D0          Hecu CO2 controller, 230Vac, RTC, 2 unipolar EEV,
di questa soluzione contribuendo all’efficienza energetica e all’affidabilità                                         connector kit, no BMS, with plastic cover, FLSMTDMCUTU
dell’intero sistema. La scheda di regolazione è predisposta per il montaggio                A ECU80TS0C0          Hecu CO2 controller, 24Vac, RTC, 2 unipolar eev,
                                                                                                                  connector kit, no BMS, FLSMTDMCUTU
su guida DIN ed è provvista di morsetti a vite estraibili ed ha integrato il
                                                                                            A ECU80TS0D0          Hecu CO2 controller, 24Vac, RTC, 2 unipolar EEV,
driver per la gestione di due valvole di espansione elettronica. È disponibile                                    connector kit, no BMS, with plastic cover, FLSMTDMCUTU
un terminale utente (PGDe o pLDpro) per le operazioni di service o messa                    A   PSD101021A        Power+ 10 A, 200-240 Vac 1Ph, IP00
in servizio dell’intero sistema.                                                            A   PSD1012200        Power+ 12 A, 200240 Vac 1Ph, IP20/IP44
                                                                                            A   PSD1016200        Power+ 16 A, 200240 Vac 1Ph, IP20/IP44
Caratteristiche principali:                                                                 A   PSD1018400        Power+ 18 A, 280480 Vac 3Ph, IP20/IP44
• Gestione modulante della potenza frigorifera tramite inverter su                          A   PS20012204110     POWER+ 12 A, 200-240 Vac 1PH, IP20 PEC
                                                                                            A   PS20015204110     POWER+ 15 A, 200-240 Vac 1PH, IP20/IP44 PEC
    compressore BLDC;                                                                       A   PS20018404110     POWER+ 18 A, 380-480 Vac 3PH, IP20/IP44 PEC
•   Gestione di un compressore a velocità fissa di backup;                                   A   PS20012204100     POWER+ 12 A, 200-240 Vac 1PH, IP20
•   Gestione di 2 ventilatori modulanti;                                                    A   PS20015204100     POWER+ 15 A, 200-240 Vac 1PH, IP20/IP44
•   Scheda con driver integrato per valvole CAREL unipolari;                                A   PS20018404100     POWER+ 18 A, 380-480 Vac 3PH, IP20/IP44
•   Gestione della valvola unipolare di alta pressione HPV;                                 A   PSACH10100        Bobina per POWER+ 18 A
                                                                                            M   E2V**CS1C0        Electronic expansion valve E2V**C 1313 S.
•   Gestione della valvola unipolare di flash gas RPRV;                                                            Steel high pressure without electrical coil
•   Comunicazione seriale con gli evaporatori (max 5);                                      M E2VSTA03*0          Unipolar stator coil with cable *mt
•   Seriale RS485 per BMS;                                                                  M E2VFIL0100          Kit filtro per valvola E2VBSF (racc. Diam.12 Odf ) 10 pz
•   Setpoint flottante di aspirazione;                                                       M SPKT00H8C0          Press.Trasd. 4-20 mA 0...120 barg (0...1740 psig) sealed gage
•   Setpoint flottante di condensazione;                                                                           8-28V packard 1/4 gas male
                                                                                            M SPKT00D8C0          Press.Trasd. 4-20 mA 0...150 barg (0…2175 psig) sealed gage
•   Algoritmo avanzato per l’iniezione calibrata di olio al compressore;
                                                                                                                  8-28V packard 1/4 gas male
•   Oil speed boost per il ritorno dell’olio al compressore;                                A   SPKT00L1S0        Press.Trasd. 0-5V 0…90 barg sealed gage packard 1/4 gas F
•   Oil recovery washing per il ritorno dell’olio al compressore;                           M   SPKC002310        Cable AWG 3 wires l=2m for SPKT packard vulcanized - IP67
•   Ampia configurazione delle funzioni di sbrinamento;                                      M   NTC0**HT41        IP55, ** m cable, 0T150 °c, multiple package (10 pcs)
•   Controllo del surriscaldamento in aspirazione e mandata;                                M   NTC0**HF01        IP67, ** mt cable, fast reading NTC probe strap-on plastic
                                                                                            O   NTC0**WH01        Wh NTC sensor IP68 -50T105 cable **m
•   Allarmistica ampiamente configurabile.
                                                                                            A   PGDEH31FX0        Terminal pGDe logo Hecu, pLAN version
                                                                                            A   PLD00GFP00        PLDPro LCD neutral, 132x64 pixels, pLAN version
                                                                                            M   S90CONN00*        Connection cable between terminal and pCO2, l=*m
                                                                                            O   PCOS004850        Opto-isolated RS485 serial connection card for pCO sistema
                                                                                            O   PCOS00S030        Fastening bracket per scheda seriale RS485/Lon/RS232
                                                                                                                                                                        Tab. 1.a
                                                                                            Legenda:
                                                                                            M    obbligatorio               A obbligatorio /               O opzionale
                                                                                                 (mandatory)                  alternativa

Esempio Hecu CO2 sistema

                                                            Supervisor

                                                                                                          RS485                               max 5 unit

                                                                                 Fig. 1.a

                                                                                    7                                             Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
ITA

                                                                                          2. INSTALLAZIONE
2.1 Scheda base: descrizione dei morsetti                                                                             Caratteristiche elettriche e meccaniche del controllo
Per ulteriori caratteristiche elettriche e meccaniche del controllo, fare Rif.                                        Alimentazione:
foglio istruzioni +050001590                                                                                          230 Vac, +10…-15% UP2A*********;
                                                                                                                      24 Vac +10%/-15% 50/60 Hz,
                                                                                                       14             28 to 36 Vdc +10…-15% UP2B*********;
                                                                                           Vout
                                                                                           RX-/TX-
                                                                                                                      Massima Potenza assorbita: 25 VA
               G         - for UP2A*: 230 Vac 50/60 Hz, +10%/-15%;                   J9    RX+/TX+     12             Isolamento tra alimentazione e controllo
      1                  - for UP2B*: 24 Vac +10%/-15% 50/60 Hz,
              G0                                                                           GND
                    J1
                                              28 to 36 Vdc +10%/-15%;
                                                                                           RX-/TX-
                                                                                                                      • mod. 230 Vac: rinforzato
                                                                        J10         J11    RX+/TX+     11             • mod. 24 Vac: rinforzato garantito dal trasformatore di alimentazione
                                                                                           GND
                                                                                                       13             Massima tensione connettori J1 e da J16 a J24: 250 Vac;
                                                                                                                      Sezioni minime dei conduttori uscite digitali: 1,5 mm2
                                                    15          J13                 J12          5a                   Sezioni minime dei conduttori di tutti gli altri connettori: 0,5 mm2
              U1
                                                                                                      16
              U2
                         J2
                                                                                           RX-/TX-                    Alimentazioni fornite
              U3                                                                    J14    RX+/TX+
                                                                                                                      Tipo: +Vdc, +5VR, Vout per alimentazioni esterne
             GND                                                                           GND
                                                                                                       10             +Vdc: 26 Vdc ±15% per mod. alimentazione 230 Vac (UP2A*********),
               U4
               U5                                                             J15                                            21 Vdc ±5% per mod .alimentazione 24 Vac (UP2B*********)
             +Vdc        J3
             +5VR                                                                         N01                                Max corrente disponibile +Vdc: 150 mA, totali prelevata da
             GND                                                               J16        NC1          9
                                                                                          C1                                 tutti i connettori, protetta da cortocircuito
      2        U6
               U7                                                                         Out2                        +5 VR: 5 Vdc ±2%; massima corrente disponibile 60 mA, totali
                                                                               J17
             +Vdc        J4                                                               C2
                                                                                                                              prelevata da tutti i connettori, protetta da cortocircuito
             +5VR                                                                         Out3
             GND                                                               J18        C2
                                                                                                                      Vout: 26 Vdc ±15% per mod. alimentazione 230 Vac (UP2A*********),
                                                                                                       8
               U8                                                                         Out4                               21 Vdc ±5% Massima corrente disponibile (J9): 100 mA
               U9                                                              J19        C2
              U10
                         J5                                                               Out5                        Caratteristiche prodotto
             +Vdc                                                              J20
             +5VR
                                                                                          C2                          Memoria programma (FLASH): 7 MB
             GND
                                                                               J21
                                                                                          C2
                                                                                                       7              Memoria dati storici: 4 MB
                                                                                          V-IN
             GND
                                                                                          Out6
                                                                                                                      Precisione orologio interno: 100 ppm
              Y1
      3
              Y2
                         J6                                                    J22        C6                          Batteria rimovibile: Lithium bottone, CR2430, 3 Vdc
              Y3                                                                          Out7                        Durata della batteria: minimo 8 anni
                                                                               J23        C7
                                                                                                       6
              DI1
              DI2                                                                         Out8                        Connessioni terminali disponibili
                                                                               J24
      4       DI3        J7          J8                                                   C8                          Tipo: tutti i terminali pGDe con connettore dedicato J15, PLD con
              DI4
             GND                                                                                                      connettore dedicato J10
                                                                                                                      Max distanza per il terminale pGDe: 2m tramite connettore telefonico
      5b                                                                                                              J15, 50 m tramite cavo schermato AWG24
                                                                                                                      Numero massimo di terminali collegabili: un terminale della serie
                                                    Fig. 2.a
                                                                                                                      pGDe su J15 o J14; un terminale PLD su connetore J10 selezionando il
Legenda:
                                                                                                                      protocollo tLAN su dip swith a bordo scheda
1  Alimentaz. 230 Vac per versione con trasformatore (UP2A*********)
   Alimentaz. 24 Vac per versione senza trasformatore (UP2B*********)                                                 Linee di comunicazione disponibili
2 Canali universali                           9 Uscita digitale di allarme                                            Tipo: RS485, Master per FieldBus1, Slave per BMS 2, pLAN
3 Uscite analogiche                           10 Connessione seriale pLAN
4 Ingressi digitali                           11 Connessione seriale BMS2
                                                                                                                      N.ro e tipo di linee disponibili:
5a Uscita valvola 1                           12 Connessione seriale Fieldbus                                         1 linea non opstoisolata su connettore J11(BMS2).
5b Uscita valvola 2                           13 Connessione per terminale PLD                                        1 linea non opstoisolata su connettore J9 (FieldBus), se non utlizzata
6 Uscite digitali a relè tipo ad interruttore 14 Dipswitch selezione
7 Ingresso tensione per uscite 2, 3, 4, 5     15 Scheda seriale RS485 BMS1                                            dal terminale PLD su connettore J10.
8 Uscite digitali in tensione                 16 Led verde di alimentazione                                           1 linea non opstoisolata su connettore J14 (pLAN), se non utlizzata dal
                                                                                                                      terminale pGDe su connettore J15.
Ingressi      Tipo: ingressi digitali a contatto pulito                                                               1 linea opzionale (J13), selezionabile tra le opz. disponbili da Carel
Digitali      Numero di ingressi digitali (DI): 4
                                                                                                                      Max. lunghezza del cavo di connessione: 2m tramite cavo non
Uscite        Tipo: 0...10 Vdc continui, PWM 0...10 V 50 Hz sincroni con l’alimentazione,
analogiche    PWM 0...10 V frequenza 100 Hz, PWM 0...10 V frequenza 2 KHz                                             schermato, 500m tramite cavo schermato AWG24
              Numero di uscite analogiche (Y): 3
Canali        Bit conversione analogico digitale: 14
                                                                                                                      Lunghezza massima connessioni
Universali    Tipo di ingresso selezionabile da applicativo: NTC, PT1000, PT500, PT100,                               Ingressi digitali universali e tutto quanto non diversamente specificato:
              4...20mA, 0...1 V, 0...5 V, 0...10 V, Ingresso digitale contatto pulito **                              inferiore a 10m
              Tipo di uscita selezionabile da applicativo: PWM 0/3,3 V 100 Hz Sincrono                                Uscite digitali: inferiore a 30m
              con l’alimentazione PWM 0/3,3 V 100 Hz, PWM 0/3,3 V 2 KHz, uscita                                       Linee seriali: si vedano indicazioni nelle relative sezioni
              analogica 0...10 V Massima corrente 2 mA
              Numero di canali universali (U): 10                                                                     Condizioni di funzionamento
              Precisione della lettura sonde passive: ± 0,5 C in tutto il range di                                    Stoccaggio: -40T70 °C, 90% rH non-cond.
              temperatura; Precisione lettura sonde attive: ± 0,3% in tutto il range di                               Funzionamento: -40T70 °C, 90% rH non-cond.
              tensione; Precisione uscite: ± 2%
Uscite        Gruppo 1, Potenza commutabile R1: NO 1(1)A                                                              Caratteristiche meccaniche
digitali      Gruppo 2, Potenza commutabile R3, R4, R5: NO NO 2(2)A                                                   Dimensioni: 13 DIN rail modules, 228 x 113 x 55 mm
              Gruppo 3, Potenza commutabile R6, R7, R8: NO 6(6)A                                                      Ball pressure test: 125 °C
              Massima tensione commutabile: 250Vac
              Potenza commutabile R2 (SSR case mounting): 15 VA 110/230 Vac                                           Altre caratteristiche
              I relè all’interno dello stesso gruppo hanno isolamento principale tra di                               Inquinamento ambientale: livello 2
              loro e deve essere applicata la stessa tensione di alimentazione                                        Grado di protezione: IP00
              I relè appartenenti a gruppi diversi hanno invece isolamento rinforzato tra                             Classe di la protezione contro le scosse elettriche: da integrare su
              di loro e può essere applicata una diversa tensione di alimentazione                                    apparecchiature di Classe I e/o II
Uscita        Massima potenza per ogni valvola: 7 W
              Tipo di piloltaggio: unipolare
                                                                                                                      PTI250 per isolamento PCB; PTI175 per gli altri materiali
Valvole
Unipolari     Connettore valvola: 6 pin sequenza fissa                                                                 Periodo delle sollecitazioni elettriche delle parti isolanti: lungo
              Alimentazione: 12 Vdc ±5%                                                                               Tipo azioni: 1C; 1Y per versioni a SSR
              Corrente massima: 0.3 A for each winding                                                                Tipo disconnessione o microinterruzione: microinterruzione
              Minima resistenza avvolgimento: 40 Ω                                                                    Categoria di resistenza al calore e al fuoco: categoria D (UL94 - V2)
              Lunghezza massima cavo: 2 m                                                                             Immunità contro le sovratensioni: categoria II
                                                                                                       Tab. 2.a       Classe e struttura del software: Classe A
** max. 6 sonde 0...5Vraz. e max.4 sonde 4...20mA                                                                     Non toccare o manomettere il dispositivo quando alimentato

Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019                                                                         8
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
ITA
2.2 Inverter monofase 10A                                                                            Conformità CE:
                                                                                                     2006/95/EC
Per ulteriori caratteristiche elettriche e meccaniche del controllo, fare Rif.                       EN 61800-5-1: Azionamenti elettrici a velocità variabile. Prescrizioni di sicurezza.
foglio istruzioni +0500076IE                                                                         Sicurezza elettrica, termica ed energetica.
                                                                                                     2004/108/EC
                                                                                                     EN 61800-3, ed.2.0: Azionamenti a velocità variabile. Requisiti EMC compresi i
                                                                                                     procedimenti di controllo speciali.
                                                                                                     EN61000-3-2: Compatibilità elettromagnetica (EMC) Parte 3-2: Limiti per le emis-
                                                                                                     sioni di corrente armonica (apparecchiature con correnti di ingresso < 16A per fase).
                                                                                                     EN61000-3-12: Compatibilità elettromag. (EMC) Parte 3-12: Limiti - Limiti per le correnti
                                                                                                     armoniche (apparecchiature con correnti di ingresso > 16 A e
Manuale d'uso OEM - High effi ciency condensing unit CO2 - CAREL
ITA
2.3        Inverter monofase 12-16 A, trifase 18-24 A                                               Conformità CE:
                                                                                                    2006/95/EC
Per ulteriori caratteristiche elettriche e meccaniche del controllo, fare Rif.                      EN 61800-5-1: Azionamenti elettrici a velocità variabile. Prescrizioni di sicurezza.
foglio istruzioni +0500048IE                                                                        Sicurezza elettrica, termica ed energetica.
                                                                                                    2004/108/EC
                                 C1                                                                 EN 61800-3, ed.2.0: Azionamenti a velocità variabile. Requisiti EMC compresi i
                                 C2
                                                                                                    procedimenti di controllo speciali.
                                                                      F                             EN61000-3-2: Compatibilità elettromagnetica (EMC) Parte 3-2: Limiti per le emissioni
                                                                                                    di corrente armonica (apparecchiature con correnti di ingresso 16A e
ITA
2.4 Inverter monofase 12A PSD2
                                                                                                                                Attenzione:
Per ulteriori caratteristiche elettriche e meccaniche del controllo, fare Rif.
                                                                                                                         • prima di effettuare qualunque intervento di manutenzione scollegare
foglio istruzioni +0500120IE
                                                                                                                           il drive e i circuiti di controllo esterni dalla rete di alimentazione elettrica
                                                       cut this area and access to DIP switches
                                                                                                                           posizionando l’interruttore generale dell’impianto su “spento”. Una
                                                       to set the ID (network) address

                                                                                     STO
                                                                                                                           volta tolta l’alimentazione al drive attendere almeno 5 minuti prima di
                 E                                                   3 4 5
                                                                                    A

                                                                                    6 7
                                                                                           B
                                                                                                                           rimuovere i cavi elettrici;
                                                                                                                         • accertarsi sempre che il motore sia completamente fermo. I motori
                                                                                                                           in rotazione libera possono causare tensioni pericolose ai morsetti di
                                            Fig. 2.f                                                                       Power+, anche quando questo non è alimentato.
Descrizione dei morsetti:
Rif.                       Descrizione                                                                                   Valori nominali
L, N                       Ingresso alimentazione monofase                                                               Nella tabella seguente sono riportati i valori nominali delle correnti
PE (*)                     Connettori Faston                                                                             di ingresso e di uscita, nonché le specifiche per il dimensionamento
U, V, W                    Uscita motore                                                                                 dei cavi (sezione, lunghezza massima) e dei fusibili. I valori sono riferiti
PE (*)                     Connettori Faston
-DC                        Uscita DC bus                                                                                 a una temperatura di funzionamento di 60 °C e a una frequenza di
+DC                        Connettori Faston                                                                             commutazione di 8 kHz, salvo diversa indicazione.
GND (0V)
                           Connessione RS485/ModBus®
Tx/Rx+                                                                                                                   PSD10102BA
Tx/Rx-                     Morsetti estraibili 3 vie
                                                                                                                         Corrente nominale di ingresso a 230V                                  19,2...16 A
STO1                       Ingresso di sicurezza STO                                                                     Fusibile o interruttore magnetotermico tipo B                         25 A
STO2                       Morsetti estraibili 2 vie                                                                     Sezione cavo di alimentazione                                         4 mm2
E                          PE     Vite di messa a terra                                                                  Corrente nominale di uscita                                           12 A
                           POWER (verde) drive alimentato                                                                Potenza nominale di uscita a 230V                                     3,8 kW
                           RUN (verde) drive in marcia
F (Led)                                                                                                                  Massima dissipazione totale                                           270 W
                           FAULT (rosso) drive in allarme
                                                                                                                         Massima dissipazione sul dissipatore                                  150 W
                           DATA (giallo) comunicazione attiva
                                                                                                                         Sezione min. cavo motore                                              2,5 mm2
                                                                                                         Tab. 2.h        Lunghezza max cavo motore                                             5m
(*)
      Le connessioni di terra all’interno del drive sono connesse tra loro e al PE.                                                                                                                 Tab. 2.i

Dimensioni
                                                                                                                                   40.9
                                                                                                  87.1

                                                                                                                                                                         197

                                                                                                                                                                               220
                                                                                                                                   177.7
                                                                                                  78

                                                 103                          39.3

                                                                                                                                                     113.4
                                                                                                                                                     148

Caratteristiche tecniche principali
 Condizioni ambientali         Temperatura di immagazzinamento        -40T60°C
                               Temperatura di funzionamento           -20T60°C
                               Umidità
ITA
Interfaccia                                                        RS 485, protocollo Modbus®, velocità di trasmissione massima 19200 bit/s - resistenza tipica in ricezione 96 KΩ
                            Collegamento dati seriale
connessione dati                                                   (pari a 1/8 unità di carico, ossia a 1/256 del carico massimo applicabile sulla linea)
                            Isolamento                             Rinforzato (circuito SELV 24V)
                            Lunghezza massima                      100 m cavo schermato
                            Grado di protezione                    IP00
                            Temperatura Ball pressure test         125°C
                            Costruzione                            Dispositivo da incorporare
                            Tipo di azione automatica              PS200122***0* and PS200122***S*                        Funzionale
                                                                   PS200122***1* and PS200122***P*                        Di sicurezza
                            Tensione di impulso                    4kV (categoria di sovratensione III)
Conformità                                                         2014/35/EU
                                          Direttiva bassa tensione
alle normative                                                     IEC 60730-1, IEC 60335-1(sez. 29 e 30), IEC 60335-2-34 (sez. 19.101 e 19.103)
                                                                   2014/30/EU
                                                                   EN 61800-3, ed.2.0: Azionamenti a velocità variabile. Requisiti EMC compresi i procedimenti di controllo
                            CE                                     speciali.
                                          Direttiva compatibilità
                                                                   EN61000-3-2: Compatibilità elettromagnetica (EMC) Parte 3-2: Limiti - Limiti per le emissioni di corrente ar-
                                          elettromagnetica
                                                                   monica (apparecchiature con correnti di ingresso < 16 A per fase).
                                                                   EN61000-3-12: Compatibilità elettromagnetica (EMC) Parte 3-12: Limiti - Limiti per le correnti armoniche (ap-
                                                                   parecchiature con correnti di ingresso > 16 A e
ITA
Caratteristiche tecniche principali
Condizioni ambientali        Temperatura di immagazzinamento        -40T60°C
                             Temperatura di funzionamento           -20T60°C
                             Umidità
ITA
Valvole E2V unipolari per R744
                             Ø 39                             B

                                               44.0
                                    Ø 16                          43.0

                                           A
                                                                       G

                                                                           ØF Out
                                                                   C

                                                                           ØF In
                                               D

                                                              G
                                                              ØE In
                                                              ØE Out
 Type valve                         A                                B                      C                         D                          E                             F                    G
 E2V**CS1C*                  125.8mm (4.95 inch)              82.3 mm (3.24inch)    52.3 mm (2.06 inch)        53.3 mm (2.10 inch)      Int.13/ Est.18 mm             Int.13/ Est.18 mm      10 mm (0.39 inch)
                                                                                                                                     (in 0.51 out 0.71 inch)       (in 0.51 out 0.71 inch)

Specifiche operative CAREL E2V-C                                                                                 Statore CAREL E2V-U
Compatibilità            R22, R134a, R404A, R407C,R410A, R744, R507A, R417A                                      Codice document. tecnica di riferimento                +050001440
Massima pressione        fino a 140 barg (2030 PSIg)                                                              Voltaggio di alimentazione                             12 V
di lavoro (MWP)
Massimo DP               fino a 120 bar (1740 PSI)                                                                Frequenza di pilotaggio                                50 Hz
di lavoro (MOPD)         per E2V24CS0** ed E2V24CS1** 85 bar (1233 PSI)
P.E.D.                   Gr. 2, art. 3, par. 3                                                                   Resistenza di fase (25 °C)                             40 Ohm ± 10%
Temperatura refrigerante -40T70 °C (-40T158 °F)                                                                  Indice di protezione                                   IP67
Temperatura ambiente     -30T70 °C (-22T158 °F)                                                                  Connessioni                                            6 poli, cavo lunghezza: 2 m
Contattare CAREL per condizioni operative diverse o refrigeranti alternativi.                                    Passi di chiusura completa / regolazione               500 / 480
                                                                                                                                                                                                      Tab. 2.d

2.6 Sonde di pressione (SPKT00**8C0)                                                                             Caratteristiche tecniche
                                                                                                                 codice documentazione                +050000596
                                                                                          A                      tecnica di riferimento
                                                                                     non utilizzato
                                                                    C                  not used                  alimentazione                       8...28 Vdc, ±20%
                                                                  uscita
                                                                   out
                                                                                                                 uscita                              4...20 mA
                                                                                                                 attacco meccanico                   ¼” gas maschio (con guarnizione circolare
                                                                                                                                                     resistente all’acqua e all’olio)
                                                                                          B                      temp. di funzionamento              -40T100°C
                                                                                    alimentazione
                                                                                        supply
                                                                                                                 temp. immagazzinamento              -20T100°C
                                                                                                                 temp. del fluido (media)             -20T100°C
                                               Fig. 2.i                                                          linearità                           ± 1 %FS (0...50 °C) compensato in temperatura)
                                                                                                                                                     ± 2 %FS (0...80 °C); ± 4 %FS (-40...100 °C)
                                                                                                                 grado di protezione                 IP67 con connettore inserito
                                                                                                                 shock                               20 g* sinusoidali, 11 msec
                                                                                                                 vibrazioni                          5...2000 Hz / 10 g /, assi X/Y/Z / 20 g sen 11 ms
Descrizione codici e modelli                                                                                     grado di inquin. amb.               normale
                                                                                                                 isolamento                          a 50 V ≥ 10 MΩ
Codice           Pressione psi Pressione bar Mod.               over       Pressione IP (1)
                                                                                                                 tempo di risposta                   (0 to 99%) < 10 msec
                                                                range      di burst
                  4 mA 20 mA 4 mA 20 mA                         psi bar psi bar                                  EMC                                 EN 61000-6-1…4 / EN 61326-2-3
SPKT00D8C0 0            2175      0          150      Maschio 4360 300 7680 530 IP67                             connessioni elettriche              Packard Plug
SPKT00H8C0        0     1740      0          120      Maschio 4360 300 7680 530 IP67                             forza di serraggio                  12...16 Nm
Nota: (1): con connettore inserito; Tutti i sensori sono di tipo sealed gauge                                    Compatibile con tutti i tipi di refrigerante
                                                                                                                Nota: FS = uscita MAX - uscita MIN

2.7 Sonde di temperatura
Modelli                                                                   NTC***HP00                                       NTC***HT41                                         NTC***HF01
Codice documentazione tecnica di riferim.                 +030220655                                      +030220655                                           +030220655
Campo di lavoro                                           -50T105 °C in aria - -50T50 °C in fluido         0T150 °C in aria                                     -50T105 °C
Connessioni                                               Terminali spellati, dimensioni: 5±1 mm          Terminali spellati, dimensioni: 6±1mm                Terminali spellati, dimensioni: 6±1mm
Sensore                                                   NTC 10 kΩ ±1% a 25 °C Beta 3435                 NTC 50 kΩ ±1% a 25 °C Beta 3977                       R(25 °C)= 10 kOhm 1%; Beta 3435
Fattore di dissipazione (in aria)                         ca. 3 mW/°C                                     ca. / approx. 3 mW                                   3 mW
Costante term. nel tempo (in aria)                        ca. / approx. 25 s                              ca. / approx. 30 s                                   ca. 50 s
Grado di protezione elemento sensibile                    IP67                                            IP55                                                 IP67
Contenitore elemento sensibile                            Poliolefina                                      Poliestere alta temperatura dim. 20x5 mm             Termoplastico con fascetta di fissaggio
Classificazione secondo la protezione                      Isolamento principale per 250 Vac               Isolamento principale per 250 Vac                    Isolamento principale per 250 Vac
contro le scosse elettriche
Categ. di resistenza al calore e al fuoco                 Non propagante la fiamma                         In accordo con CEI 20-35                             Cavo UL/HB

                                                          •   temperatura interno banco                   •     temperatura di scarico
                                                                                                                                                               •   temperatura evaporazione
                                                                                                                                                               •   temperatura di uscita del gas cooler
                                                                                                                                                                                                       Tab. 2.e

Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019                                                                 14
ITA
2.8 Schema generale di collegamento
                                       Inverter 15A (1 PH)                Inverter 18/24A (3 PH)                                                                  Inverter 12A
                                       Inverter 12/16A (PSD1)                                                                                                     Inverter 10A (PSD1)

                                                                                                                                               PE                                                -DC
                                                                                                                                                                      L                          +DC
                                    L1/L L2/N L3        U    V   W              GND +   -    STO                                                                      N                                 GND +   -   STO
                                                                                                                                                                          U       V       W
                                                                                                                                                 K                                                        3 4 5 6 7

                             K                                                                                                                                                                                            PTC   Klixon
                                                   PE
                                                                                                                                       High press
                 HP switch                                                                                                                switch
                                                             M                                                                                                 Fuse or     M
                                                                                                                                                                MCB
                          Fuse or
                            MCB
                                                            3                                      PTC    Klixon                                                          3

                                      L    N                                                                                                           L   N

                                                                            to HECU controller                                                                                                  to power+, MPXPRO, Ultracella

                      PAY ATTENTION                                                                                                       2
                      TO THE POWER SUPPLY!                                                                                                1
                                                                                                                                              ON OFF
                                                                                                                                                                Vout
                                                                                                   HECU configuration                                           RX-/TX-
        Power supply                                                       G                                                                     J9             RX+/TX+
                                                                                                           DIP2=OFF
        - for ECU70*: 230 Vac 50/60 Hz, +10%/-15%;
                                                                          G0
                                                                                                           DIP1=ON
                                                                                                                                       J10                      GND
        - for ECU80*: 24 Vac +10%/-15% 50/60 Hz,                                 J1                                                                             RX-/TX-
                          28 to 36 Vdc +10%/-15%;                                                                                              J11              RX+/TX+
                                                                                                                                                                GND                                                                 boss

           Analog Input
                                                                                                     RS485 serial card
                                                                                                           to connect                          J12                                                 HPV valve
         B1                                         White                U1                        supervisory system
                                                    White                U2                                                                                     RX-/TX-
               Suction press. probe (*)                                                 J2
                                                                         U3
                                                                                                                                 J13           J14              RX+/TX+
                                                    Green               GND                                                                                     GND
                                                    Green
                                                                          U4
         B2                                                               U5
                                                    Black
               Gas cooler press. probe (*)
                                                                        +Vdc            J3
                                                    Black               +5VR                                                                                   N01                    N
                                                                                                                                                                          Fan 1
         B3                                                             GND                                                               J16                  NC1
                                                                                                                                                                                                  pGDe Terminal                 pLD PRO
               Suction temp. probe (CAREL NTC)                                                                                                                 C1                     L
                                                                          U6
         B4                                                               U7                                                                                   Out2
               Discharge temp. probe (CAREL NTC-HT)                                                                                       J17                  C2
                                                                        +Vdc            J4
         B5                                                             +5VR                                                                                   Out3
               Gas cooler temp. probe (CAREL NTC)
                                                                        GND                                                               J18                  C2
         B9                                                               U8                                                                                   Out4
                                                    White                 U9                                                              J19                  C2                     L N
               Discharge only LT probe (*)          Green
                                                    White                U10
               Parallel suct. probe (LT) (*)
                                                    Black               +Vdc            J5                                                J20
                                                                                                                                                               Out5
                                                    Black
                                                                                                                                                               C2
         B10                                                            +5VR
                                                    Green                                                                                                      C2
                                                                                                                                                                                                          Digital Output
               Receiver probe (MT) (*)                                  GND
                                                                                                                                          J21                  V-IN                                         (POWERED)
                                                                         GND
                                 0...10 Vdc Fan                                                                                                                N06
                                                                     (A01) Y1
                                                                                        J6                                                J22                  C6
                                                                     (A02) Y2
           Analog Output (0-10V)                                     (A03) Y3                                                                                  N07
                                                                                                                                          J23
                                                                         DI1
                                                                                               J8                                                              C7

                                                                         DI2                                                                                   N08                                       Digital Output
                                                                                                                        RPRV valve        J24                                                          (NOT POWERED)
                                                                         DI3            J7                                                                     C8
                                                                         DI4
           Digital Input (free voltage)                                 GND

                                                                                                                      Fig. 2.j

(*) Le sonde di pressione 4-20mA vanno collegate con il White (bianco) a Ux e il Black (nero) a +Vdc, Green (verde) non utilizzato

       Attenzione: Se non si usano gli inverter in versione PEC (con struttura del software di classe B) le sicurezze di protezione termica per sovraccarico e
per alta pressione devono agire direttamente sull’attuatore del compressore e quindi vanno cablate in serie con il comando della bobina del contattore
compressore. Per le tipologie di cavo da utilizzare fare riferimento al manuale power+ (cod. +0300094IT).

Tabelle selezione I/O (esempio unità MT)

Ingressi Analogici                                                        Ingressi Digitali                                      Uscite Analogiche                                                     Uscite Digitali

Temperatura di aspirazione                                                Allarme di alta pressione                              Ventilatori modulanti                                                 Ventilatore 1
Temperatura di scarico                                                    Allarme di bassa pressione                                                                                                   Ventilatore 2
Temperatura esterna                                                       Allarme compressore BLDC                                                                                                     Valvola solenoide di equalizzazione
Temperatura di uscita del gas cooler                                      Allarme ventilatori
Pressione di aspirazione                                                  ON-OFF remoto
Pressione del gas cooler
Pressione del ricevitore

                                                                                                                        15                                                                    Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019
ITA
2.9 Schemi funzionali                                                              2. Configurazione per Bassa Temperatura
                                                                                   La configurazione prevista per le applicazioni di bassa temperatura prevede
Le configurazioni previste sono due, una per applicazioni di media
                                                                                   che Hecu CO2 gestisca due compressori DC (BT/LT e Parallelo), un massimo
temperatura ed una per applicazioni di bassa temperatura. La principale
                                                                                   di 2 ventilatori on-off, una valvola di espansione elettronica per la regolazione
differenza consiste nella doppia linea di aspirazione, necessaria in caso
                                                                                   della pressione del gas cooler (HPV) ed una valvola di espansione elettronica
di applicazioni di bassa temperatura, in questo caso l’installazione della
                                                                                   per la gestione della pressione del ricevitore (RPRV) opzionale. Si precisa
valvola RPRV (flash gas) è opzionale.
                                                                                   che in questa configurazione l’installazione della valvola RPRV (flash gas) è
Ci sono poi configurazioni alternative che prevedono l’utilizzo di un
                                                                                   opzionale in quanto la regolazione della pressione del ricevitore è demandata
sistema per l’iniezione di olio tramite EEV (utilizzando un driver esterno)
                                                                                   al compressore Parallelo.
o capillare.
                                                                                   La rete seriale consente il monitoraggio e l’interazione con un massimo di 5
                                                                                   evaporatori dotati di MPX PRO o UltraCella e valvola di espansione elettronica
                                                                                   CAREL EEV.
1. Configurazione per Media Temperatura
La configurazione prevista per le applicazioni di media temperatura
prevede che Hecu CO2 gestisca un compressore DC, un massimo di 2
                                                                                                                                                T
ventilatori on-off, una valvola di espansione elettronica per la regolazione                  P               Check                              OUT, GT
                                                                                                  GC
della pressione del gas cooler (HPV) ed una valvola di espansione                                            valve
                                                                                             T    DIS
elettronica per la gestione della pressione del ricevitore (RPRV). La rete                                                                          2

seriale consente il monitoraggio e l’interazione con un massimo di
5 evaporatori dotati di MPX PRO o UltraCella e valvola di espansione                                                                      HPV
                                                                                                          By-pass
elettronica CAREL EEV.                                                                   Technology

                                                                                                                     L1: PAR
                                                         T                                   T   SUC

          P    GC
                          Check                          OUT, GT
                          valve                                                              P   SUC
                                                                                                                                                        P   REC
          T    DIS
                                                             2

                                                                                                 Check                             35 barg
                                                                                                 valve
                                                   HPV
                       By-pass    2                                                          P    DIS
      Technology
                                                                 P   REC                     T    DIS

                           RPRV
                                             35 barg

                                                                                                          By-pass
          T   SUC                                                                        Technology

          P   SUC
                                                                                                                    L2: LT
                                                                                             T   SUC

                                         2
                                                                                             P   SUC

                     up to 5
                                                                                                                               2

                                                                                                        up to 5

                                         2
                                                                                                                               2

                                                                                                                               Fig. 2.l
                                        Fig. 2.k
                                                                                   Simbolo                Descrizione
                                                                                   TS,LT                  Suction temperature LT
Simbolo                Descrizione                                                 PS,LT                  Suction pressure LT
TSUC                   Suction temperature                                         TD,LT                  Discharge temperature LT
PSUC                   Suction pressure                                            PD,LT                  Discharge pressure LT
TDIS                   Discharge temperature                                       TS,PAR                 Suction temperature PAR
Tout,GC                Gas cooler temperature                                      PS,PAR                 Suction pressure PAR
PGC                    Gas cooler pressure                                         TD,PAR                 Discharge temperature PAR
PREC                   Receiver pressure                                           Tout,GC                Gas cooler temperature
                                                                                   PGC                    Gas cooler pressure
                                                                                   PREC                   Receiver pressure

Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019                                     16
ITA
3 . Configurazione rete seriale
Hecu CO2 è dotato di una linea seriale RS485 Fieldbus integrata e di una
linea seriale RS485 BMS. Nella linea seriale RS485 Fieldbus possono essere
configurati 2 inverter power+ e fino a 5 MPXPRO/Ultracella. Gli indirizzi
seguono la seguente tabella. Per agevolare la fase di commissioning con
impostazioni di default è consigliabile configurare gli MPXPRO/Ultracella
con indirizzi consecutivi a partire da indirizzo 11. La tabella seguente
mostra i valori predefiniti degli indirizzi seriali per MPXPRO/Ultracella
connessi.
     Dispositivo                                  Indirizzo                          Dispositivo                                                    Indirizzo
       Power+                                         1                           MPXPRO/Ultracella 3                                                  13
       Power+                                         3                           MPXPRO/Ultracella 4                                                  14
  MPXPRO/Ultracella 1                                11                           MPXPRO/Ultracella 5                                                  15
  MPXPRO/Ultracella 2                                12

L'indirizzo seriale 3 viene utilizzato per l'inverter del compressore parallelo
quando è presente nell'applicazione LT.

       Note: Per le unità LT i due inverter devono essere indirizzati il primo al
n. 1 e il secondo al n. 3. Per ottenere questi indirizzi (1 e 3) si deve fare
l'impostazione sui rispettivi dip switch a 0 e 2 che poi sommati all'indirizzo
base (1) daranno l'indirizzo finale n. 1 e n. 3 (vedi paragrafo "Indirizzo di rete"
a pag. 13).

                                                                                         1                                                                                                    3

                                     Supervisory
                                     system
                                                                                                   C1      C1                                                                                      C1       C1
                                                                                                   C2      C2                                                                                      C2       C2

                                                                                                                                                      F                                                                                            F

                                                                                               PE                                                                                                 PE
                                                                                                        L1/L L2/N L3            U   V   W                                                                L1/L L2/N L3       U    V   W
                                                                                                                                            1 2 3 4 5 6 7 8 9 10                                                                         1 2 3 4 5 6 7 8 9 10

                                                                    Fieldbus - Modbus® RS485
                                                                                                                                                                                                                                                                                               max 5 units
       RX+/TX+

       RX+/TX+
       RX-/TX-

       RX-/TX-
       GND

       GND
       Vout

                    J9

                               J11

                                     J12

                                            J14
           ON OFF

                                                        J16

                                                              J17

                                                                     J18

                                                                           J19

                                                                                 J20

                                                                                       J21

                                                                                             J22

                                                                                                        J23

                                                                                                                 J24
                         J10
   2
       1

                                                                                                                                                                                     MPXPRO                             MPXPRO
                                            J13

                                                                                                                   RPRV valve

                                                                                                                                                                            High                              High
                                                                                                                                                                           voltage                           voltage

                                                                                                                                                                          master                         master
                                                                                                                                                                                                                                                       master        EVDEVO       master      EVDEVO
                                                                                                         J8

                                                                                                                                                                    AUX                            AUX
                                           J2

                                                   J3

                                                                J4

                                                                                 J5

                                                                                             J6

                                                                                                                       J7
                           J1

                                                                                                                                                                          11                               12                                                   13                     14

                                                                                                                                                               Fig. 2.m

Nota: comunicazione di sistema è compatibile solo con MPXpro SW.

                    Attenzione:
• Un eventuale corto circuito sulla linea seriale Field bus compromette il
  funzionamento del compressore del sistema.
• Non essendoci un controllo software sul dispositivo (MPXpro,
  Ultracella) collegato, fare attenzione, in fase di configurazione, ad
  impostare correttamente gli stessi in funzione dell'indirizzo fisico
  selezionato nel controllo dell'evaporatore.
• Per la selezione dell'indirizzo di power+, MPXpro, Ultracella fare
  riferimento ai relativi manuali.

     Attenzione: Il sistema è compatibile solo con MPXpro con revisione
SW ≥ 4.0 e UltraCella con revisione SW ≥ 2.0

                                                                                                                                                                                     17                                                                               Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019
ITA
2.10 Installazione                                                                             Attenzione: nel collegamento dei controlli è necessario rispettare
Per l’installazione procedere come indicato di seguito, facendo riferimento             le seguenti avvertenze:
agli schemi elettrici:                                                                  • il non corretto collegamento alla tensione di alimentazione può
• prima di effettuare qualsiasi operazione sulla scheda del controllo,                      danneggiare seriamente il controllo;
  togliere l’alimentazione principale portando l’interruttore principale                • utilizzare capicorda adatti per i morsetti in uso. Allentare ciascuna vite
  del quadro elettrico su OFF.                                                             ed inserirvi i capicorda, quindi serrare le viti e tirare leggermente i cavi
• evitare di toccare a mani nude la scheda del controllo, in quanto                        per verificarne il corretto fissaggio;
  eventuali scariche elettrostatiche potrebbero danneggiare i                           • separare quanto più possibile i cavi delle sonde e degli ingressi digitali
  componenti elettronici;                                                                  dai cavi dei carichi induttivi e di potenza per evitare possibili disturbi
• un grado di protezione elettrica adeguato all’applicazione deve                          elettromagnetici. Non inserire mai nelle stesse canaline (comprese
  essere assicurato dal costruttore del banco frigo o da un opportuno                      quelle dei quadri elettrici) cavi di potenza e cavi sonde;
  montaggio del controllo;                                                              • evitare che i cavi delle sonde siano installati nelle immediate vicinanze
• nel caso di più condensing unit connesse allo stesso quadro elettrico                    di dispositivi di potenza (contattori, interruttori magnetotermici, ecc.);
  generale usare una protezione differenziale di Tipo B o B+, se si usa                  • Ridurre il più possibile il percorso dei cavi delle sonde ed evitare che
  un inverter per il pilotaggio del compressore, inoltre tale protezione                   compiano percorsi che racchiudano dispositivi di potenza.
  deve essere installata sempre a monte dei Tipo AC/A/F (vedi figura
  sottostante):
                                                                                               Attenzione: Struttura del software in classe A: le sicurezze di
                                                                                        protezione termica per sovraccarico e per alta pressione devono agire
                                                                                        direttamente sull’attuatore del compressore e quindi vanno cablate in
                                                                                        serie con il comando della bobina del contattore compressore.
               Wh
                             OK                                                                Note: il collegamento seriale parte dal morsetto J10 di Hecu CO2 e
                                                                                        passa per l’inverter power+ e per tutti gli MPXPRO installati nelle unità
                                                                                        interne refrigerate. Il numero massimo di MPXPRO è 5, limitato per questa
               Tipo
              AC/A/F                                                                    applicazione.
                           IΔn≥300 mA S                                                 Si raccomandano i seguenti suggerimenti:
                                                                                        • collegare i due cavi intrecciati ai morsetti Tx/Rx+ e Tx/Rx-;
                                                                                        • collegare il cavo singolo al morsetto GND;
                                                                                        • collegare lo schermo (calza) a terra solo da un lato;
                                  NO                                                    • utilizzare un cavo schermato (es. Belden 3106A – AWG 22);
               Tipo                            Tipo                                     • Per il solo collegamento ad una rete seriale di supervisione: collegare
              AC/A/F                           B/B+                                        una resistenza di terminazione da 120 Ω tra i morsetti Tx/Rx+ e Tx/Rx-
                           IΔn≤100 mA                  kHz   IΔn≥30 mA                     dell’ultimo controllo della rete (il più lontano da Hecu).

                                                                                                Earth

                                    Fig. 2.n                                                                    Signals (+/-)
                                                                                                                GND
• collegare gli eventuali ingressi digitali, Lmax=10m;
• collegare le sonde di temperatura e di pressione, Lmax=10m;
• collegare il cavo delle valvole di espansione elettronica ai connet. J17
  e J21;
• collegare al morsetto J10 il cavo di comunicazione seriale con l’inverter
  (se presente);                                                                                        AWG 20/22
• collegare il terminale PGDe (necessario per la messa in servizio) al
  connettore J17;
• collegare l’alimentazione elettrica al controllo e all’eventuale relativo
  inverter;                                                                                 Device                              Device                      Device
                                                                                            1                                   2                           n
• programmare il controllo, eseguendo la procedura guidata di messa in
  servizio: vedere il capitolo “Messa in Servizio”.
• è preferibile collegare i carichi elettrici alle uscite a relè, solo dopo aver
  programmato il controllo. Si raccomanda di valutare attentamente
  la portata massima dei relè di uscita indicata nelle Caratteristiche
  tecniche;
• collegare la linea seriale di supervisione alla schedina opzionale BMS
  RS485.

       Attenzione: evitare l’installazione dei controlli in ambienti con le
seguenti caratteristiche:
• umidità relativa maggiore del 90% o condensante;
• forti vibrazioni o urti;
• esposizione a spruzzi d’acqua;
• esposizione ad atmosfere aggressive ed inquinanti (es: gas solforici
  e ammoniacali, nebbie saline, fumi) per evitare corrosione e/o
  ossidazione;
• alte interferenze magnetiche e/o radiofrequenze (evitare quindi
  l’installazione degli apparecchi vicino ad antenne trasmittenti);
• esposizioni dei controlli all’irraggiamento solare diretto e agli agenti
  atmosferici in genere.

Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019                                          18
ITA

                                                          3.        INTERFACCIA UTENTE
3.1 Terminale grafico                                                                        Schermata di menu
Hecu CO2 si interfaccia all’utenza mediante il terminale pGDE, a pannello                    Nel caso di schermate di menu, un esempio è mostrato in figura:
o built-in. Le funzioni associate ai 6 tasti del terminale pGDE sono le
medesime in tutte le schermate e sono descritte in tabella.

Funzioni dei 6 tasti
         Tasto     Funzione associata
           (ALARM) Visualizza la lista degli allarmi attivi e permette l’accesso allo
                   storico degli allarmi
                   Permette di entrare nell’albero del menu principale

                      Torna alla maschera di livello superiore
                                                                                                                                  Fig. 3.b
           (UP)    Scorre una lista verso l’alto oppure permette di aumentare il
                   valore evidenziato dal cursore
           (DOWN) Scorre una lista verso il basso oppure permette di diminuire il            Nell’angolo in alto a destra sono mostrati il numero di voce selezionato
                   valore evidenziato dal cursore                                            tra quelle presenti. Mediante i tasti    e     si seleziona la voce di menu
           (ENTER) Entra nel sottomenu selezionato o conferma il valore impo-
                   stato
                                                                                             desiderata e con      si accede alla voce selezionata.
                                                                             Tab. 3.a
I led associati ai tasti hanno il seguente significato.
                                                                                             Schermata di visualizzazione/impostazione parametri
Significato dei LED                                                                          Un esempio di schermata di visualizzazione/impostazione dei parametri
LED        Tasto   Significato                                                               è mostrato in figura, dove sono evidenziati anche i campi e le icone
Rosso              Lampeggiante: presenza di allarmi attivi e non riconosciuti               utilizzate:
                   Fisso: presenza di allarmi riconosciuti
Giallo             Hecu CO2 acceso

Verde              Hecu CO2 alimentato                                                           1                                                                   2
                                                                             Tab. 3.b
                                                                                                 3
3.2 Descrizione display
Esistono tre tipi fondamentali di schermate mostrate all’utente:
• Schermata principale                                                                                                            Fig. 3.c
• Schermata di menu
• Schermata di visualizzazione/impostazione parametri                                        1       Identificativo ramo di menu
                                                                                             2       Identificativo di schermata
                                                                                             3       Parametri

Schermata principale                                                                         L’identificativo di schermata individua in maniera univoca il ramo di menu
La schermata principale è la maschera a cui il software a bordo di Hecu                      e la schermata: i primi caratteri indicano il ramo di menu mentre le ultime
CO2 ritorna automaticamente dopo 5 minuti dall’ultima pressione di un                        due cifre alfanumeriche individuano la schermata all’interno del menu,
tasto. Un esempio di schermata principale è mostrato in figura, dove                          ad esempio la schermata Bab01 è la prima schermata del menu B.a.b.
sono evidenziati anche i campi e le icone utilizzate:

  1
  2
  3                                                                            4
                                                                               5
                                        Fig. 3.a
1 Ora e data
2 Grandezze principali.
3 Stato unità (con macchina spenta) o stato compressori e ventilatori (con mac-
  china accesa)
4 Segnalazioni allarmi attivi e stato funzionamento manuale
5 Accesso alle ulteriori maschere di informazione (ramo di menu A.a) tramite il
   tasto ENTER        .

         Nota:
• Le informazioni mostrate in schermata principale variano secondo
  la configurazione di impianto e il tipo di grandezza utilizzata per la
  regolazione (pressione, temperatura).

                                                                                        19                                        Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019
ITA

                                                      4. DESCRIZIONE MENU
4.1 Menu principale

Per navigare all’interno dell’albero usare i tasti:                           a.Info princ.
                                                                              b.Setpoint
                                                             A.Stato unità    c.ON/OFF
                                                                              a.Stato               a.Ingr.digitali
                                                                                                    b.Ingr.analog.
                                                                                                    c.Usc.digitali
                                                                                                    d.Usc.analog.
                                                                              b.Gest.manuale        a.Usc.digitali
                                                                                                    b.Usc.analog.
                                                                                                    c.usc.BLDC
                                                                                                    d.vacuum
•         e       : navigazione all’interno dei
                                                                              c.Test                a.Usc.digitali
    sotto-menu, maschere, e range di valori e
                                                             B.Ingr./Usc.                           b.Usc.analog.
    impostazioni;                                                             a.MT/LT compr.        a.Stato I/O
                                                                              b.PAR compr.(ONLY LT) b.Regolaz.
•      : confermare e salvare le modifiche                                                           c.Ore funz.
    apportate;                                                                                      d.Risparmio En.
                                                                                                    e.Allarmi
                                                                                                    f.Configuraz.
•      : per tornare al menù precedente                      C.Compressori                          g.Avanzati
                                                                                                    a.Stato I/O
                                                                                                    b.Regolaz.
                                                                                                    c.EEV
                                                                                                    d.Risparmio En.
                                                                                                    e.Allarmi
                                                                                                    f.Configuraz.
                                                             D.Condensatori                         g.Avanzati
                                                                                                    a.Stato I/O
                                                                                                    b.configurazione
                                                                                                    c.regolazione
                                                             E.evaporatori                          d.driver EVD
                                                                              a.Olio                a.Stato I/O
                                                                                                    b.Impostaz.
                                                                              b.defrost             a.Stato I/O
                                                                                                    b.Impostaz.
                                                                                                    c.info
                                                                              c.Economizz.          a.Stato I/O
                                                                                                    b.Regolaz.
                                                                              d.Injection           a.Stato I/O
                                                                                                    b.regolazione
                                                                              e.Recupero calore     a.Stato I/O
                                                                                                    b.Regolaz.
                                                                              f.Funz.generiche      a.Stadi
                                                                                                    b.Modulazioni
                                                                                                    c.Allarmi
                                                                                                    d.Fasce orarie
                                                                                                    e.Stato I/O
                                                                              g.Chillbooster        a.Stato I/O
                                                                                                    b.Regolaz.
                                                                              h.Transcritical       a.I/O
                                                                                                    b.settings
                                                                                                    c.EVOsettings
                                                                              1.DSS                 a.Stato I/O
                                                             F.Altre funz.                          b.settings
                                                                              a.Orologio            a.Fasce orarie
                                                                                                    b.Aggiustam.
                                                                              b.Lingue
                                                                              c.BMS
                                                                              d.Fieldbus
                                                             G.Impostaz.      e.Password
                                                                              a.Storico
                                                                              b.Prevent
                                                             H.Sicurezze      c.Config.allarmi

                                                             I.Info
                                                                              a.Pre-configurazioni   non disponibile
                                                                              b.Wizard
                                                                              c.Config.avanzata      non disponibile
                                                             L.Setup          d.Default

Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019                        20
ITA

                                                       5. MESSA IN SERVIZIO
5.1 Procedura guidata di messa in servizio                                            Maschera Lb08: indica il setpoint e il differenziale per la regolazione del
                                                                                      compressore scelti come default da CAREL in accordo con la tipologia di
La prima configurazione di Hecu CO2 può essere eseguita dal terminale
                                                                                      applicazione e refrigerante. Il tipo di regolazione è sempre proporzionale
utente pGDe o pLDpro. Se il controllo non è ancora stato configurato, il
                                                                                      più integrale ed in uscita dal wizard la regolazione sarà esclusivamente
terminale utente mostrerà la prima maschera di una procedura guidata
                                                                                      con setpoint fisso fino a che non verrà configurata la comunicazione
di configurazione, denominata wizard. Si può accedere alternativamente
                                                                                      con i banchi che consentirà di implementare il setpoint flottante di
a tale menù dal ramo: L Setup >> b.wizard.
                                                                                      aspirazione.
Di volta in volta vengono proposti i parametri principali, necessari ad
una prima programmazione dell’unità. Le maschere del wizard sono
tutte numerate nell’angolo in alto a destra; nella spiegazione seguente
si farà riferimento a tale numerazione. Per muoversi da una maschera alla
successiva premere È, per tornare alla maschera precedente premere Ç.

Maschera Lb01: indica la tipologia di installazione che può essere di
media o bassa temperatura.

                                                                                      Maschera Lb91: Indica il numero di ventilatori. È possibile selezionare al
                                                                                      massimo 2 ventilatori.

Maschera Lb02: cambio unità di misura da SI (°C, barg) a Imperiale (°F, psig).

Maschera Lb03: indica la tipologia e il numero di compressori.

                                                                                      Maschera Lb92: indica la tipologia di ventilatori tra ON-OFF e modulanti
                                                                                      PWM o 0-10V.

                                                                                      Maschera Lb95: indica la regolazione del gascooler in temperatura.

                                                                                      Maschera Lb96 Lb97: indica la tipologia di regolazione e il valore del
                                                                                      setpoint e del differenziale di lavoro dei ventilatori.

                                                                                      Maschera Lb99: indica quali valvole sono state installate nell’unità per la
Maschera Lb04: indica la tipologia di dispositivo modulante assocciato al
                                                                                      gestione della CO2 e la tipologia
compressore selezionato nella maschera precedente.

Maschera Lb05: Indica il modello del compressore BLDC e l’indirizzo
seriale dell’inverter power+ (sempre=1). Consente poi di capire se
l’inverter è acceso e connesso in seriale con il Hecu.

                                                                                      Maschera Lb3a: indica la fine della procedura di wizard. Premendo il
                                                                                      tasto ENTER la procedura ha termine e inizia la configurazione del sistema
                                                                                      seguendo le scelte effettuate.

Maschera Lb06: indica se il modello di inverter collegato è compatibile
e in caso affermativo procede con lo scaricamento automatico di alcuni
parametri caratteristici del modello compressore nell’inverter. È possibile
inoltre forzare la scrittura dei parametri in maniera manuale selezionando
“Yes” su Scrivi default.

                                                                                           Attenzione: attendere alcuni secondi per l’avvio della procedura
                                                                                      automatica di scaricamento dei default e la sua conclusione.

Maschera Lb07: indica il tipo di regolazione del compressore in pressione,
e il relativo refrigerante.
                                                                                 21                                     Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019
ITA

                                                                 6. FUNZIONI
6.1 ON/OFF dell’unità                                                                Hecu CO2 scarica in maniera automatica i parametri ottimizzati per
                                                                                     ciascun modello di compressore al termine della procedura di wizard.
L’unità può essere accesa e spenta da:
                                                                                     Nel caso di cambio modello del compressore o del power+ è possibile
• Terminale utente                                                                   configurare il nuovo sistema manualmente dal menù Compressori Æ
• Supervisore                                                                        Advanced Æmaschera Cag01.
• Ingresso digitale
                                                                                     Hecu CO2 e power+ devono essere alimentati e collegati in seriale, il
L’On-Off da terminale utente ed i parametri di impostazione sono
                                                                                     dispositivo power+ deve avere indirizzo 1 (default).
raggiungibili da menu principale, ramo A.c.
                                                                                     Il tipo di compressore deve essere selezionato dalla lista dei compressori
L’On-Off da supervisore e da ingresso digitale e l’accensione dopo il black           disponibili; il numero di poli e il modello corretto di Power+ sono definiti
out (con il relativo ritardo, per evitare continue accensioni e spegnimenti          automaticamente.
in caso di instabilità dell’alimentazione) devono essere abilitati.
Il funzionamento dell’On-Off da ingresso digitale, funziona come una
abilitazione, cioè se l’ingresso digitale è Off l’unità non può essere accesa
in nessun altro modo, mentre se è On, può essere accesa o spenta in
qualsiasi altro modo, con uguale priorità (vince l’ultimo comando inviato,
qualsiasi sia la provenienza), come mostrato in figura:

      Digital Input
                                                                                     Su Set defaults selezionare YES e premere INVIO.
     User interface
                                                                                     Se il modello di power+ (letto dal power+) è lo stesso modello o più
        Supervisor                                                                   grande del power+ selezionato in base al tipo di compressore BLDC i
                                                                                     default possono essere scritti e Hecu CO2 può pilotare il compressore. In
       Unit On/Off                                                                   caso contrario apparirà il messaggio “Not compatible”.

                                  Fig. 6.a
      Nota: Esistono condizioni particolari o funzioni del software Hecu
                                                                                     Gestione inviluppo
      CO2 che richiedono lo spegnimento:
• Configurazione di alcuni parametri: es. ingressi/uscite, configurazione              L’inviluppo è l’insieme dei punti di lavoro di un compressore nei quali esso
  dei compressori, parametri inverter.                                               può operare in sicurezza per un tempo indefinito. Esso è rappresentabile
• Installazione dei default                                                          graficamente disegnando i limiti all’interno dei quali vanno mantenute
• Gestione manuale                                                                   le condizioni operative. In figura è riportato l’inviluppo dei compressori
                                                                                     Toshiba serie DY/RY.

                                                                                               Discharge
                                                                                                pressure
6.2 Compressore BLDC                                                                            Pd max
É possibile configurare massimo 2 compressori BLDC pilotati via inverter
Power+. Il tipo di compressore viene selezionato in Compressori Æ
Configurazione (Cag01).
Il compressore BLDC è gestito via Modbus e funziona solo se accoppiato
ad un inverter CAREL power+. Nel caso non sia presente comunicazione
con l’inverter, il compressore non potrà funzionare.
A seguire la lista dei compressori attualmente disponibili:                                      Pd min

                                                                                                           Ps min                 Ps max Suction
Media e Bassa temperatura con PSD1 (R744)                                                                                                 pressure
Compressore          HPV            RPRV         Inverter        Capacità                                              Fig. 6.b
                statore unipolare E2VSTA0310                  Tevap. = -10°C
                                                               TGC = 32°C
TOSHIBA DY30     E2V09CS1C0     E2V11CS1C0     PSD101021A       0,3...2,8 kW         I limiti dell’inviluppo sono costituiti da:
TOSHIBA DY45     E2V11CS1C0     E2V14CS1C0     PSD1012200       0,5...4,2 kW         •   Minima e massima pressione di scarico
TOSHIBA DY67     E2V14CS1C0     E2V18CS1C0     PSD1016200       0,7...6,3 kW         •   Minima e massima pressione di aspirazione
TOSHIBA RY100    E2V18CS1C0     E2V24CS1C0     PSD1018400       1,0...8,8 kW         •   Minimo e massimo rapporto di compressione (CR)
                                                                     Tab. 6.a        •   Massima corrente assorbibile dal compressore
Media e Bassa temperatura con PSD2 (R744)                                            Le condizioni operative sono definite da:
Compressore      HPV           RPRV             Inverter         Capacità            • Pressione di aspirazione
                  statore unipolare                           Tevap. = -10°C         • Pressione di scarico
                     E2VSTA0310                                TGC = 32°C            • Temperatura di scarico
TOSHIBA DY30 E2V09CS1C0 E2V11CS1C0           PS200122041*0      0,3...2,8 kW
TOSHIBA DY45 E2V11CS1C0 E2V14CS1C0           PS200122041*0      0,5...4,2 kW         • Velocità di rotazione (rps)
TOSHIBA DY67 E2V14CS1C0 E2V18CS1C0           PS200152041*0      0,7...6,3 kW
TOSHIBA RY100 E2V18CS1C0 E2V24CS1C0          PS200184041*0      1,0...8,8 kW         La pressione di scarico massima può essere limitata per esigenze
                                                                     Tab. 6.a        costruttive del circuito in questo caso avremo una limitazione alla
* =0: versione no PEC; *=1: versione PEC                                             massima temperatura di scarico. La forma dell’inviluppo può cambiare
                                                                                     con la velocità del compressore, e con essa le condizioni operative
      Note: verificare su ksa.carel.com la lista aggiornata dei compressori           ritenute sicure per il compressore. È possibile quindi che una certa coppia
      disponibili, facendo riferimento al documento "DC compressor                   di pressioni di lavoro sia considerata sicura (all’interno dell’inviluppo) a
availability table" codice +050001835.                                               una certa velocità e non sicura (fuori inviluppo) ad un’altra velocità.
Configurazione manuale                                                               Qualora le condizioni operative siano vicino al limite dell’inviluppo o

Hecu CO2 +0300085IT rel. 2.2 - 07.05.2019                                       22